Uninterruptable Power Supply

From SME Server
Revision as of 10:33, 27 February 2007 by Snoble (talk | contribs) (split howto into individual pages)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigationJump to search

Nut UPS – Uninterruptable Power Supply

The primary goal of the Network UPS Tools (NUT) project is to provide reliable monitoring of UPS hardware and ensure safe shutdowns of the systems which are connected.

Standard configuration

Obtain your configuration values
Find your model here http://www.networkupstools.org/compat/stable.html
Type is only used if your model is genericups
note. /dev/ttyS0 = com1, [if using USB]

set configuration values

config setprop nut Device /dev/ttyS0
config setprop nut Model apcsmart 
config setprop nut Type 7
config setprop nut status enabled 

check

config show nut

apply changes and restart server

signal-event post-upgrade ; signal-event reboot 

confirm server is communicating with UPS

upsc UPS@localhost

Emails are sent to admin whenever a UPS event occurs

Configuring as a slave

where 192.168.33.11 is your UPS master, the computer that will communicate with the UPS The hostname of the server may also work.

set configuration values

config setprop nut SlaveUPS UPS@192.168.33.11
config setprop nut Master no

apply changes and restart server

signal-event post-upgrade ; signal-event reboot 

confirm server is communicating with master

upsc UPS@192.168.33.11

Conecting multiple UPS's

to be added http://bugs.contribs.org/show_bug.cgi?id=629