Difference between revisions of "Uninterruptable Power Supply"

From SME Server
Jump to navigationJump to search
m
m (serial cables)
Line 16: Line 16:
 
Find your Model here http://www.networkupstools.org/compat/stable.html <br />
 
Find your Model here http://www.networkupstools.org/compat/stable.html <br />
 
Type is only used if your model is genericups <br />
 
Type is only used if your model is genericups <br />
 +
Note, standard serial cables won't work with your USB, use the supplied one
  
 
  config setprop nut Model apcsmart  
 
  config setprop nut Model apcsmart  

Revision as of 02:56, 15 June 2007

Nut UPS – Uninterruptable Power Supply

The primary goal of the Network UPS Tools (NUT) project is to provide reliable monitoring of UPS hardware and ensure safe shutdowns of the systems which are connected.

Standard configuration

If using USB just enable nut

config setprop nut status enabled

These are only for information as they are the default values

config setprop nut Model newhidups (default)
config setprop nut Device /var/lib/ups/hiddev0 (default/USB)

Not all UPS's are supported by USB or the newhidups driver, refer to the link below
eg. config setprop nut Model bcmxcp_usb is for some Powerware units on USB
or config setprop nut Model genericups is for other Powerware units that only work on serial

Find your Model here http://www.networkupstools.org/compat/stable.html
Type is only used if your model is genericups
Note, standard serial cables won't work with your USB, use the supplied one

config setprop nut Model apcsmart 
config setprop nut Device /dev/ttyS0
config setprop nut Type 7
config setprop nut status enabled 

check

config show nut

apply changes and restart server

signal-event post-upgrade ; signal-event reboot 

alternatively

expand-template /etc/sysconfig/ups
expand-template /etc/ups/ups.conf
expand-template /etc/ups/upssched.conf
expand-template /etc/ups/upsmon.conf
expand-template /etc/ups/upsd.users
expand-template /etc/ups/upsd.conf
/etc/rc7.d/S15nut restart

confirm server is communicating with UPS

upsc UPS@localhost

Emails are sent to admin whenever a UPS event occurs

Configuring as a slave

where 192.168.33.11 is your UPS master, the computer that will communicate with the UPS The hostname of the server may also work.

set configuration values

config setprop nut SlaveUPS UPS@192.168.33.11
config setprop nut Master no

apply changes and restart server

signal-event post-upgrade ; signal-event reboot 

confirm server is communicating with master

upsc UPS@192.168.33.11

Conecting multiple UPS's

to be added http://bugs.contribs.org/show_bug.cgi?id=629